Pollution Prevention Guidelines (PPG2) Above Ground Oil Storage Tanks, State Under 7. Ancillary Equipment: The fill point is where the tanker delivery pipework/hose connects to fill the tank. They recommend the fill point should be at the tank & within the secondary containment system or in a suitable cabinet with a drip tray to catch any oil spilled during deliveries. Fill point drip trays should be: Clean, free from water & other debris before each use. Large enough to hold all the oil that could be lost when the fill point shut off valve has been closed & the delivery hose is disconnected. Able to be removed without the risk of spilling oil (min capacity 3L). Checked after each delivery & if necessary safely emptied before being put away.

Fill Point Cabinet – 2" Single Fill (Top Entry) Wall mounting steel cabinet.

Integral drip tray with sight gauge.

Lever ball valve to isolate line.

Non return valve to prevent line draining.

Parallel thread connection with aluminium cap.

Hinged door with lockable handle.

Pre-threaded mounting holes on back plate for tank gauges & alarms (order separately).

Other versions available (7 days delivery), including dual fill and left or right side entry. Enquire with customer service team for P+A on alternative options.